Simulation of Single-phase to Ground Fault to Anticipate Against the Sympathetic Tripping Phenomena
Abstract
Simulation of single-phase to ground fault (1Φground
fault) to anticipate against the sympathetic tripping
phenomena have been done. Results include are the current
value of single-phase to ground fault and capacitive current
and the value of adjustment current of Ground Fault Relay
(GFR) is 0.5 amperes (10% of the value of the ratio of
current transformer in term of the secondary side) for all
feeders, the selected time setting of GFR is 0.30, and Time
Multiplier Setting of Ground Fault Relay values obtained
for all feeders is 0.15 (rounded from 0.11). The largest
current value occurred in a location 25% length of the line
for all feeders. It was influenced by the value of reactance as
the denominator value, the smaller the percentage of length
of the line, the greater the value of the fault current. The
value of adjustment current was obtained at 0.5 amperes and
working time of Ground Fault Relay not more than 0.4
seconds.